Dielectric Boot Resistance Data.

Every Dielectric boot is tested to EN50321 before leaving the factory.

Dielectric boots will withstand a voltage of 20KV plus for over 8 hours. To carry out this test, the boot is filled with steel balls to 40mm from the top of the boot and immersed in water to the same height.

Whilst the EN 50321 standard requirement is only 10KV for 3 minutes, using the same test method on Dielectric boots at 5KV, the leakage current is <5mA. An additional test is carried out at 7.5 KV where the leakage current is 7.5mA.

The sole will withstand over 35KV for 1 minute when filled with steel balls to a level just above the ankle.

Dielectric boots surpass the following international standards.

 

Standard Test Voltage Leakage Current Test Method
CSA Z195-02 18 KV <1mA sole
ASTM F2413-05 14 KV <3mA sole
ASTM F1117-93 5 KV 0.22mA* sole
ASTM F1117-93 10 KV 0.48mA* sole
ASTM F1117-93 15 KV 0.76mA* sole
ASTM F1117-93 30 KV 2.36mA* sole
* Typical values